LOCATION

MGK Kemayoran LT.GF Blok C.1 No.5

Jual Sanwa HG561H Insulation Tester

Specifications Sanwa HG561H Insulation Tester

Function Measuring range Best accuracy Resolultion
15/25/50V 9.99M/21.0MΩ
100/125/250/500V
9.99M/99.9M/110MΩ
±(2%+5) 0.1MΩ
Rated voltage 15/25/50/100/125/250/500V
ACV/DCV 600V(Automatic measurement for AC/DC) ±(1.6%+7) 0.1V
Ω 999.9/99.99k/999.9kΩ ±(1.5%+7) 0.1Ω
Insulation resistance (Level meter) 15/25/50V 5 Levels (LED light up/blinking)
100/125/250/500V 7 Levels (LED light up/blinking)
Continuity ≦ approx.30Ω: Beep sounds
Rated current 1.0~1.2mA
Battery LR03(AAA alkaline battery)×4
Size/Mass H139×W91×D29mm/Appox. 230g
Earth lead(Black) Length Approx. 1.8m
Safety standard IEC61010 CAT.Ⅲ 300V CAT.Ⅱ 600V

Optional Accessories:

  • TestLeadSet:TL-BP
  • TestLead:TL-28
  • Adapter:TL-A18,TL-A51

Deskripsi

Sanwa HG561H Insulation Tester

Karya Mandiri Techindo has a wide range of Sanwa products – search by type, or model, or filter by brand to find the one you are after. If you still can’t find it contact us..

Features Sanwa HG561H Insulation Tester

  • Electrical circuit not more than Low voltage 600V,
  • Insulation resistance of Electric installation, voltage measurement(DC/AC auto detect),
  • Resistance measurement, and Continuity check
  • Automatically-held readings after measuring MΩ
  • The LED level meter shows the reading
  • The instrument makes only necessary voltages enabled between 15V, 25V, 50V, 100V, 125V, 250V, and 500V
  • Easy-to-read LCD with the fixed decimal point
  • Provides the probe that enables you to measure through a hole of a circuit breaker cover
  • The lighting lamp illuminates a place to be measured, and the LCD has a backlight.