FLUKE 1746-30-INTL POWER QUALITY LOGGER W/60 CM 3,000A IFLEX

  • Functions: Voltage, current, power, power factor, frequency; Energy forward/reverse; Peak Demand; THD; Voltage and current harmonics (to 50th); Flicker; Unbalance
  • Rapid voltage change events; Interharmonics (to 50th); Dips, swells, interruption and transient events tables; Mains signaling; Inrush current
  • Recording: Trend

Deskripsi

Accuracy
Voltage Range: 1000 V
Maximum resolution: 0.1 V
Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.1 % of nominal voltage
i17xx-flex 3000IP 24 3000 A Range: 300, 3000 A
Maximum resolution: 0.01 A (min. 3.0 A)3, 0.1 A
Intrinsic accuracy at reference conditions (% of reading +% of range): ±(1% + 0.03%)
Voltage Range: 42.5 to 69 Hz
Maximum resolution: 0.01 Hz
Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.1%)2
Auxiliary Input Range: ±10 V DC
Maximum resolution: 0.1 mV
Intrinsic accuracy at reference conditions (% of reading +% of range): ±(0.2% + 0.02%)
Voltage Min/Max Range: 1000 V
Maximum resolution: 0.1 V
Intrinsic accuracy at reference conditions (% of reading +% of range): ±0.2 % of nominal input voltage
Current Min/Max Range: Defined by accessory
Maximum resolution: Defined by accessory
Intrinsic accuracy at reference conditions (% of reading +% of range): ±(5% + 0.2%)
THD on Voltage Range: 1000%
Maximum resolution: 0.10%
Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
THD on Current Range: 1000%
Maximum resolution: 0.10%
Intrinsic accuracy at reference conditions (% of reading +% of range): ± 2.5%
Voltage Harmonics 2nd to 50th Range: 1000 V
Maximum resolution: 0.1 V
Intrinsic accuracy at reference conditions (% of reading +% of range): ≥1 V: ±5% of reading, <1 V: ±0.05 V
Current Harmonics 2nd to 50th Range: Defined by accessory
Maximum resolution: Defined by accessory
Intrinsic accuracy at reference conditions (% of reading +% of range): ≥3% of current range: ±5% of reading, <3% of current range: ±0.15% of range
Flicker PLT, PST Range: 0 to 20
Maximum resolution: 0.01
Intrinsic accuracy at reference conditions (% of reading +% of range): 5%
Electrical Specifications
Voltage Range 100 to 500 V using safety plug input when powering from the measurement circuit
100 to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power Consumption Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency ≥68.2% (in accordance with energy efficiency regulations)
Maximum No-Load Consumption <0.3 W only when powered using IEC 60320 input
Mains Power Frequency 50/60 Hz ±15%
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-Battery Runtime Typically 4 hours
Charging Time <6 hours
Data Acquisition
Resolution 16-bit synchronous sampling
Sampling Frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input Signal Frequency 50/60 Hz (42.5 to 69 Hz)
Circuit Types 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ
delta open leg, currents only (load studies)
Data Storage Internal flash memory (not user replaceable)
Memory Size Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic Interval
Measured Parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging Interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging Time Min/Max Values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
Demand Interval (Energy Meter Mode)
Measured Parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured Parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging Interval 10 min for all parameters
2 hrs (long term Flicker PLT)
150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual Harmonics 2nd to 50th harmonic
Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics 1st to the 50th interharmonic
Total Harmonic Distortion Calculated on 50 voltage harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered Recordings RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)
Waveform of voltage and current up to 200 ms, 10/12 cycles
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120 s
Inrush RMS profile based on ½ cycle RMS steady state triggering
Flicker In accordance with IEC 61000-4-15 and IEEE 1453
Mains Signaling Two user defined frequencies up to 3 kHz
PQ Health Summarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160 Compliance with standard
Programmable PQ Limits Enables user defined limits for local standards compliance
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power Quality IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
Power IEEE 1459
Power Quality Compliance EN 50160
Safety General: IEC 61010-1: Pollution Degree 2
Measurement: IEC 61010-2-033: CAT IV 600 V/CAT III 1000 V
Power Supply: Overvoltage Category IV, Pollution Degree 2
Li-ion Battery: IEC 62133
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
Wi-Fi File transfer and remote control via direct connection or Wi-Fi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability)
USB-Mini Data download device to PC
Voltage Inputs
Number of Inputs 4 (3 phases referenced to neutral)
Maximum Input Voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Measurement Category 1000 V CAT III/600 V CAT IV
Current Inputs
Number of Inputs 4 (3 phases and neutral), mode selected automatically for attached sensor
Input Voltage Clamp input: 500/50 mVrms; CF 2.8
Rogowski coil input: 150/15 mVrms at 50 Hz, 180/18 mVrms at 60 Hz
CF 4 all at nominal probe range
Range 1 to 150 A/10 to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
Bandwidth 42.5 Hz to 3.5 kHz
Scaling 1:1 and variable
Auxiliary Inputs
Number of Inputs 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input Range 0 to ± 10 V DC, or 0 to ± 1000 V DC (with optional adapter), 1 reading/s
Scale Factor Format: mx + b (gain and offset) user configurable
Displayed Units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth Connection
Number of Inputs 2
Supported Modules Fluke Connect® 3000 series
Acquisition 1 reading/s
Environmental Specifications
Operating Temperature -13 to 122°F (-25 to 50°C)
Storage Temperature Without battery: -13 to 140°F (-25 to 60°C)
With battery: −4 to 122°F (-20 to 50°C)
Operating Humidity IEC 60721-3-3: 3K6:
-13 to 86°F (-25 to 30°C): ≤100%
104°F (40°C): 55%
122°F (50°C): 35%
Operating Altitude 6561.7′ (2000 m) up to 13,123.4′ (4000 m) derate to 1000 V CAT II/600 V CAT III/300 V CAT IV
Storage Altitude 39,370.1′ (12,000 m)
Enclosure IEC 60529: IP50
IEC 60529: IP65 with IP65 rated voltage connector
Vibration IEC 60721-3-3 /3M2
Electromagnetic Compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A
IEC 61000-6-5 Power station environment
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
General Specifications
Dimensions 9.1 x 7.1 x 2.1″ (23 x 18 x 5.4 cm)
Weight 2.2 lbs (1 kg)
Tamper Protection Accept securing cables (max. Φ 6mm)